THERMATEC Products - heat pumps, hydraulic cabinets, DHW and buffer tanks

COMMERCIAL SOLUTIONSTHERMATEC PLUS C LINE Heat Pumpscommercial solutions

An ultra-efficient heat pump system, THERMATEC PLUS C LINE, with a high power range from 50 kW to 800 kW in cascade. THERMATEC PLUS C LINE heat pumps offer the possibility of individually adjusting the system to the needs of your facility. Our heat pumps are perfect for heating various large-scale facilities.

Technical specificationHeat pump THERMATEC PLUS C LINE:Technical specification

  • TH-R290-C50-3P
Heat pump Thermatec TH-R290-C50-3P
Parameters Unit TH-R290-C50-3P
Power supply / 380–415V / 3N~ / 50Hz
Moc nominalna kW 48.17
Heating (A7/W35)
Heating capacity range kW 17.56 – 55.30
Input power kW 3.15 – 14.85
COP kW/kW 3.72 – 5.57
Heating (A7/W55)
Heating capacity range kW 17.95 – 51.20
Input power kW 5.42 – 19.20
COP kW/kW 2.67 – 3.31
Cooling (A35/W12)
Cooling capacity range kW 10.00 – 32.00
Input power kW 3.84 – 13.30
SCOP average (THW at 35°C) kWh/kWh 3.92
SCOP average (THW at 55°C) kWh/kWh 3.25
Rated input power kW 19.84
Rated input current A 30.3
Refrigerant TYPE / CHARGE / GWP - / kg /- R290 / 2 x 2.5 / 3
CO2 Equivalent TCO2eq 0.015
Operation pressure (low side) MPa 0.8
Operation pressure (high side) MPa 3.0
Maximum allowable pressure MPa 3.0
Electrical shockproof Class I
Protection class IP IPX4
Maximum outlet water temperature °C 75
Operationg ambient temperature °C -25 ~ 45
Water piping connections cal G1 1/2
Rated water flow m³/h 8.6
Water pressure drop kPa 6.5
Water pressure (min. - max.) MPa 0.1 – 0.3
Sound pressure (1 m) dB(A) 60
Net dimensions (L x W x H) mm 1155 x 990 x 1880
Net weight kg 500

NOMINAL TEST CONDITIONS
Heating (A7/W35): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 30°C/35°C
Heating (A7/W55): Outdoor temperature 7°C/6°C (DB/WB) Water inlet/outlet 47°C/55°C
Cooling (A35/W12): Outdoor temperature 35°C/24°C (DB/WB) Water inlet/outlet 12°C/7°C